Megger DET62D

Digital earth tester

Megger DET62D
  • Earth Resistance Ranges (Autoranging) 200Ω Range: 0,1 Ω to 199,9 Ω 2 kΩ Range: 0,001 kΩ to 1,999 kΩ
  • Accuracy (at 23°C) ±2 % of reading ±3 digits Total service error ±5 % of reading ±3 digits
  • Display 3 1 /2 digit L.C.D. with Ω, kΩ and low battery voltage indicators. LEDs for high noise, high voltage probe resistance and high current loop resistance
  • Test Frequency 128 Hz ±0,5 Hz
  • Test Voltage Maximum 50 V peak.
  • Test Current (constant within a range) 200 Ω Range: 1 mA a.c. r.m.s. 2 kΩ Range: 100 µA a.c. r.m.s.
  • Simple to use, one touch operation
  • Auto switch off to save battery power
  • Rugged, weatherproof case
  • Large, clear L.C.D.
  • Indicators show if reading may be invalid
  • Terminal shorting bars supplied
  • Earth testing kits available
  • Optional carrying case and harness
  • Three-terminal measurement for ground electrode testing
  • Superior noise rejection to 40 V
  • Suitable for the testing of single ground electrodes or measuring the resistance of conductors
  • Ground resistance can be measured directly from 100 m W to 2 k W