ASCO Avtron 2500
Portable Suitcase AC Load Bank
- Load Capacity: up to 100kW at 240V and 480V AC, 3-Phase, 60Hz, Derates to 80kW at 208V AC, 3-Phase, 60Hz; 52.8kW at 240V AC, 1-Phase, 60Hz; and 13.3kW at 120V AC, 1-Phase, 60Hz
- Duty Cycle: Rated for Continuous Operation
- Load Step Resolution: 12.5kW Minimum at 240V and 480V AC, 3-Phase; Derates at Other Voltages
- Controls: Local Manual Control Panel Includes Main Power On-Off Switch
- Instrumentation: Digital Monitoring via Full Digital Metering (V, A, Hz, kW) with Automated Data Acquisition and Real Time Data Logging, Software IrDA Converter Supplied
- Control/Cooling Power: Requires 120V Single-Phase 60Hz Power Source; Line Cord Provided
- Cooling System: Approximately 2112 CFM Cooling is Provided by Eight Integral Cooling Fans
- Load Elements: Industrial Grade Resistor Wire Elements, Wound and Supported on Mica Base
- Safety Features: Cooling Air Loss Protection, Fuses for Short-Circuit Protection
- Load Connections: Quick Disconnect Cam-Type Male Connectors on the Front of the Load Bank
- Load Cable Set: Standard 10ft Three Phase Load Cable Set with Mating Female Connectors and Lugs